FAQs Técnicas

Realizar una pregunta

Cúal es el reemplazo de los interruptores SquareD de frame FAL?

El reemplazo directo se describe a continuación en la siguiente tabla:
Breaker Amps Trip Range Replacement Trip Range
FAL3600311M 3 8-28 HJL36030M71 9-325
FAL3600712M 7 18-70 HJL36030M71 9-325
FAL3601513M 15 50-180 HJL36030M71 9-325
FAL3603013M 30 50-180 HJL36030M71 9-325
FAL3603015M 30 100-350 HJL36030M71 9-325
FAL3605014M 50 75-260 HJL36050M72 84–546
FAL3605016M 50 150-580 HJL36050M72 84–546
FAL3610016M 100 150-580 HJL36100M73 180–1040
FAL3610018M 100 300-1100 HJL36100M73 180–1040
FAL3615024M 150 450-1100 HJL36150M74 348–1690
 
Breaker Amps Trip Range Replacement Trip Range
FHL3600311M 3 8-28 HJL36030M71 9-325
FHL3600712M 7 18-70 HJL36030M71 9-325
FHL3601513M 15 50-180 HJL36030M71 9-325
FHL3603013M 30 50-180 HJL36030M71 9-325
FHL3603015M 30 100-350 HJL36030M71 9-325
FHL3605014M 50 75-260 HJL36050M72 84–546
FHL3605016M 50 150-580 HJL36050M72 84–546
FHL3610016M 100 150-580 HJL36100M73 180–1040
FHL3610018M 100 300-1100 HJL36100M73 180–1040
FHL3615024M 150 450-1100 HJL36150M74 348–1690
¿Ha sido útil?
¿Qué podemos hacer para mejorar la información?